Schneider Electric 140DRA84000 Modicon Quantum Relay Output Module Overview
Electrical Specifications and Contact Ratings
- Brand & Series: Manufactured by Schneider Electric for the Modicon Quantum automation platform.
- Output Configuration: Provides 16 discrete relay outputs with 1 normally open (NO) contact per channel, Form A type.
- Voltage Range: Supports 20…250V AC, 30…150V DC, and 5…30V DC for maximum application flexibility.
- Current Capacity: Handles 2A resistive load at 250/30V AC/DC up to 60°C, with 1A for inductive or tungsten loads.
- Surge Protection: Includes internal varistor protection at 275V to suppress output voltage transients.
- Switching Capacity: Delivers 500VA resistive switching capacity with 10A surge current capability for 10ms capacitive loads.
Performance Characteristics and Durability
- Response Time: Features 10ms turn-on time (0 to 1) and 20ms turn-off time (1 to 0) maximum.
- Mechanical Life: Rated for 10 million mechanical cycles, ensuring long-term reliability in high-cycle applications.
- Electrical Durability: Achieves 200,000 cycles at 2A 250V AC resistive load and 100,000 cycles at 2A 30V DC resistive.
- Isolation Ratings: Provides 1780Vrms AC isolation between channels and bus for 1 minute, plus 2500V DC isolation.
- Power Dissipation: Dissipates 5.5W plus 0.5W per active point, requiring 1100mA from the Quantum bus.
Environmental Specifications and Certifications
- Operating Temperature: Functions reliably in 0 to 60°C (32 to 140°F) ambient industrial environments.
- EMC Immunity: Withstands 4kV contact ESD and 8kV air discharge per IEC 801-2 standards.
- Field Resistance: Resists electromagnetic fields of 10V/m from 80 to 2000 MHz per IEC 801-3.
- Certifications: Holds FM Class 1 Division 2, GOST, ABS, C-tick, UL 508, and CSA C22.2 No 142 approvals.
- Altitude Rating: Suitable for installation at altitudes up to 5000m (16404 ft) without performance degradation.
Frequently Asked Questions (FAQ)
- Q: What is the exact model number for this Modicon Quantum relay module?
A: The module is the Schneider Electric 140DRA84000 with 16 discrete relay outputs. - Q: What contact configuration does the 140DRA84000 use?
A: Each of the 16 channels uses 1 normally open (NO) contact with Form A configuration. - Q: What is the maximum current rating for this relay output module?
A: The module supports 2A resistive load at 250/30V AC/DC at 60°C ambient temperature. - Q: How quickly do you ship the 140DRA84000 module?
A: We process and dispatch orders within 5 days via DHL, UPS, or FedEx carriers. - Q: What is the return policy for this Schneider Electric output module?
A: We offer 30-day returns on all brand new original automation components. - Q: Can this module switch both AC and DC loads?
A: Yes, the 140DRA84000 handles 20-250V AC, 30-150V DC, and 5-30V DC applications.